CVE-2026-9637
View CSAF Summary The following versions of Rockwell Automation Logix Platform are affected: ControlLogix 5580 <=V33, V34.011-V34.014, V35.011-V35.013, V36.011-V36.012 (CVE-2026-9637, CVE-2026-9637, CVE-2026-9637, CVE-2026-9637) CompactLogix 5380 <=V33, V34.011-V34.014, V35.011-V35.013, V36.011-V36.012 (CVE-2026-9637, CVE-2026-9637, CVE-2026-9637, CVE-2026-9637) GuardLogix 5580 <=V33, V34.011-V34.014, V35.011-V35.013, V36.011-V36.012 (CVE-2026-9637, CVE-2026-9637, CVE-2026-9637, CVE-2026-9637) Compact GuardLogix 5380 <=V33, V34.011-V34.014, V35.011-V35.013, V36.011-V36.012 (CVE-2026-9637, CVE-2026-9637, CVE-2026-9637, CVE-2026-9637) CVSS Vendor Equipment Vulnerabilities v3 7.5 Rockwell Automation Rockwell Automation Logix Platform Improper Restriction of Operations within the Bounds of a Memory Buffer Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: United States Vulnerabilities Expand All + CVE-2026-9637 A denial-of-service vulnerability exists in the affected Logix platforms due to improper validation of input length during CIP message processing. This can result in a major nonrecoverable fault (MNRF), requiring a power cycle to recover. View CVE Details Affected Products Rockwell Automation Logix Platform Vendor: Rockwell Automation Product Version: Rockwell Automation ControlLogix 5580 <=V33, Rockwell Automation ControlLogix 5580 V34.011-V34.014, Rockwell Automation ControlLogix 5580 V35.011-V35.013, Rockwell Automation ControlLogix 5580 V36.011-V36.012, Rockwell Automation CompactLogix 5380 <=V33, Rockwell Automation CompactLogix 5380 V34.011-V34.014, Rockwell Automation CompactLogix 5380 V35.011-V35.013, Rockwell Automation CompactLogix 5380 V36.011-V36.012, Rockwell Automation GuardLogix 5580 <=V33, Rockwell Automation GuardLogix 5580 V34.011-V34.014, Rockwell Automation GuardLogix 5580 V35.011-V35.013, Rockwell Automation GuardLogix 5580 V36.011-V36.012, Rockwell Automation
CSIRTS triage
- What
- Improper restriction of operations within memory buffer bounds allows out-of-bounds memory access.
- Who is affected
- Critical manufacturing environments worldwide running affected ControlLogix, CompactLogix, GuardLogix, and Compact GuardLogix 5380/5580 controllers.
- Urgency
- Critical severity with CVSS 7.5 and no active exploitation reported; immediate patching required for industrial control systems.
- Action
- Update to patched versions of Logix Platform controllers; contact Rockwell Automation for available fixed versions.
AI-assisted analysis generated from the source advisory — verify against the original.
⚡ Watch CVE-2026-9637
Get an email if CVE-2026-9637 is added to CISA KEV, gains public exploit code, or a new advisory cites it — max one per day, one-click unsubscribe.
Exploitation outlook
- Low exploitation risk0.31% 30-day exploitation probability — currently an unlikely target, but scores change as exploit code circulates. Riskier than 24% of all EPSS-scored CVEs.
Advisory coverage (3)
- medium[NEW] [medium] Rockwell Automation ControlLogix 5580, CompactLogix 5380, and CompactLogix 5480: Multiple vulne…cert-bund · 2026-09-02
- unknownCVE-2026-9637: A denial-of-service security issue exists in the affected Logix platforms listed in the table a…nvd · 2026-09-01
- criticalRockwell Automation Logix Platformcisa · 2026-09-01
External references
Embed the live status
— this badge updates automatically when the KEV or exploit status changes. How to embed it →
[](https://www.csirts.com/cve/CVE-2026-9637)